• Air insulated metal clad construction using high quality steel
  • Durable epoxy powder coated finish
  • Compartmentalized and compact design
  • Easy accessibility for maintenance
  • Meters, relays, and controls are located at a convenient height
  • Extensible on both sides
  • Side cable box for single panels
  • Compatible with state-of-the-art numerical protection
  • Fully type tested as per IEC 60298/IS 3427
  • We can also offer outdoor versions
Technical Specification of Vacuum Circuit Breaker Cubicles

Up to 11kV 22kV 33kV
Indoor Indoor Indoor Indoor Indoor
Type A 12 62D A 12 63G MYK-12 MYK-24 MYK-36
Rated Voltage kV 12 12 12 24 36
Insulation level kVrms / kVp 28 / 75 28 / 75 50 / 125 50 / 125 70 / 170
Rated Current A Up to 1250 2500 3150 1250 1250
Braking Capacity kA 26.2 40 40 26.2 26.2
Dimensions
(WXDXH)
mm 650 x 1670 x 2000 /
800 x 1650 x 2000
1000 x 2000 x 2100 1100 x 2000 x 2300 1100 x 2000 x 2300 1500 x2900 x 2400
Degree of Protection kVrms / kVp IP4X IP4X IP4X IP4X IP4X
Weight Of Each Cubicle kG 800 1100 1100 1100 1600

Leave A Comment