FEATURES | VALUES/ STANDARDS |
---|---|
Ambient Temperature | -10 to +50°C |
Altitude | Not exceeding 1000mtrs above mean sea level. |
Atmosphere | Non corrosive & non hazardous |
Relative Humidity | Up to 100% |
Voltage | 415V ±10% , 3 ph. |
Frequency | 50Hz ±5% |
Combined Variation | 10% |
Duty | S1 (continuous) |
Service factor | 1.0 |
FEATURES | VALUES/ STANDARDS |
---|---|
Starting | Star Delta |
Permissible starts/hr | Cold successive – 4 , Hot successive; – 3 , Equally spread – 6 |
Loading at reduced volts | 75% Rated volts for 5 minutes |
Insulation / temp.rise | Class `F’ / 70°C |
Direction of rotation | Bi-directional |
No. Of leads | 6 |
Connection | Delta for all frames |
Degree of protection | IP 22 for SA/VSA series up to 225 Frames, IP 23 for SA/VSA series – 250 to 355 Frames |
Method of cooling | IC 01 |
T.box position | RHS looking from DE. |
Bearing life (90% survival basis) |
40,000 working hrs. For direct drive 20,000 working hrs. For belt drive |
Vibration | Normal class as per is 12075 |
Noise | As per IS 12065 |
Construction | Foot mounted / ‘B’ flange mounted |
Frame sizes | SA / VSA 180 to 355. (for ‘B’ flange mounting ratings covered in SA180M to be offered in VSA180L, & ratings covered in SA200M to be offered in VSA200L) |
Shaft extension | Single cylindrical extension as per IS 1231 |
Body material | Cast iron |
T.box material | Cast iron up to 225 frames, mild steel for 250 to 355 Frames |
Fan material | Aluminium for all 2 pole ratings of SA frame & all ratings of VSA frame, Polypropelene for 4, 6, & 8 pole ratings of SA180 to 225 frame, mild steel for 250 to 355 – 2pole, Mild steel / Aluminium for 250 to 355 frames – 4, 6, and 8 poles. |
Accessories |
Nil. |
Paint & shade | NC base RAL5012 shade up to 225, Epoxy base RAL5012 above 225 |
Bearing type Greasing facility |
Open type ball/roller bearings Online greasing facility for all |
FEATURES | VALUES/ STANDARDS |
---|---|
Ambient Temperature | -10 to +50°C |
Altitude | Not exceeding 1000mtrs above mean sea level. |
Atmosphere | Non corrosive & non hazardous |
Relative Humidity | Up to 100% |
Voltage | 415V±10% , 3 pH |
Frequency | 50Hz ±5% |
Combined Variation | 10% |
Duty | S1 (continuous) |
Service factor | 1.0 |
FEATURES | VALUES/ STANDARDS |
---|---|
Starting | Star Delta/DOL (with shorting links but with 2 entries) |
Permissible starts/hr. | Cold successive – 4 hot successive – 3 equally spread – 6 |
Loading at reduced volts | 75% Rated volts for 5 minutes |
Insulation / temp.rise | Class `F’ / 70 deg. C |
Direction of rotation | Bi-directional |
No. Of leads | 6 |
Connection. | Delta |
Degree of protection | IP 55 |
Method of cooling | IC 411 |
T.box position | RHS looking from driving end |
Bearing life (90% survival basis) |
40,000 working hrs. For direct drive 20,000 working hrs. For belt drive |
Vibration | Normal class as per IS 12075 |
Noise | As per IS 12065 |
Construction | Foot, ‘B’ flange, Foot cum ‘B’ flange |
Frame sizes | SC 180 to 355 (For ‘B’ flange mounting, ratings covered in SC180M to be offered in VSC180L, & ratings covered in SC225S to be offered in VSC225M) |
Shaft extension | Single cylindrical extension as per IS: 1231 |
Body material | Cast iron |
T.box material | Cast iron up to 225 frame, mild steel for 250 to 355 frame |
Fan material | Polypropelene for 4, 6, & 8 pole & cast iron for 2 pole up to 225 frames. Mild steel for 250 to 355 frames for all polarities |
Accessories |
Nil |
Paint & shade | NC base RAL5012 shade up to 225, Epoxy base RAL5012 above 225 frame |
Bearing type and Greasing facility |
Open type bearings for SC180 to 355 Online greasing facility for SC180 to 355 |
FEATURES | VALUES/ STANDARDS |
---|---|
Ambient Temperature | -10 to +50°C |
Altitude | Not exceeding 1000mtrs above mean sea level. |
Atmosphere | Non corrosive & non hazardous |
Relative Humidity | Up to 100% |
Voltage | 415V±10% , 3 ph. |
Frequency | 50Hz ±5% |
Combined Variation | 10% |
Duty | S1 (continuous) |
Service factor |
1.0 |
FEATURES | VALUES/ STANDARDS |
---|---|
Starting | DOL for all (single entry upto 132,double entry for 160 with links) Or Star delta for frames 112 & above. |
Permissible starts/hr | Cold successive – 4 , Hot successive – 3 , Equally spread – 6 |
Loading at reduced volts | 75% Rated volts for 5mins |
Insulation / temp.rise | Class `F’ / 70°C |
Direction of rotation | Bi-directional |
No. Of leads | 3 up to 100 & 6 for frame 112 & above. |
Connection | Star: up to 90 frame and 6 & 8 pole ratings of 100 frame |
Delta: 2 & 4 pole ratings of 100 frame & 112 and above all ratings | |
Degree of protection | IP 55 |
Method of cooling | IC 411 |
T.box position | RHS looking from driving end towards DE |
Bearing life |
40,000 working hours. For direct drive |
Vibration | Normal class as per IS 12075. |
Noise | As per IS 12065. |
Construction | Foot, ‘B’ flange, ‘C’ Flange , Foot cum ‘B’ flange, Foot cum ‘C’ Flange |
Frame sizes | PRIMO 63 to 160 |
Shaft extension | Single cylindrical extension as per IS 1231 |
Body material | Aluminium (Diecast) up to 112, cast iron for 132 to 160 |
T.box material | Nylon 6 up to 132, Aluminium (die cast) for 160 |
Fan material | Polypropelene |
Accessories |
Nil |
Paint & shade | NC base RAL 5012 shade |
Bearing type and Greasing facility |
Pre lubricated sealed bearings No online greasing facility |
FEATURES | VALUES/ STANDARDS |
---|---|
Ambient Temperature | 0 to +45°C |
Altitude | Not exceeding 1000mtrs above mean sea level. |
Atmosphere | Non corrosive & non hazardous |
Relative Humidity | Up to 100% |
Voltage | 415V±10% (Can also be offered upto 650V) |
Frequency | 50Hz. ±5% |
Combined Variation | Any combination of voltage and frequency |
FEATURES | VALUES/ STANDARDS |
---|---|
Starting | Stator Rotor Starter/Liquid Rotor Starter |
Permissible starts/hr. | 2 Hot Or 3 Cold or 4 Equally spread |
Loading at reduced volts | These motors are designed to run at 75% of rated supply voltage for a duration of five minutes. |
Insulation / temp.rise | Class F/F |
Temp rise Stator/Rotor | Class B/F |
Direction of rotation | Bi-directional |
No. Of leads | TR 5&6 > ST: 6 and RT: 3 Rest 3 / 3 |
Degree of protection | IP23 |
Method of cooling | IC01 |
T.box position | Left hand side when viewed from non-drive end, reversible assembly at site is not possible. |
Terminal box arrangement | For KCW 450 & 500: Stator – 43506201, Rotor – 43521599. For KCW 560: Stator – 41102205, Rotor – 43506101. Terminal box rotatable through 3600 in steps of 180° (i.e cable entry possible from top or buttom) |
Bearing life(90% survival basis) | Lithium based grease to “Grade 3” as per IS: 7623 for 4 pole & above motors. |
Lubricant | Direct drives: 40,000 working hours.(Based on 90% survival life) |
Vibration | Normal class as per IS: 12075. |
Noise | As per IS: 12065. |
Shaft extension. | Single cylindrical extension as per IS: 1231. |
Body material | Mild Steel |
T.box material | Mild Steel |
Fan material | Mild Steel |
Accessories |
Refer to Kirloskar Electric engineering department. |
Paint & shade | Epoxy “RAL BLUE” to shade plate K-102 |
Bearing type and Greasing facility |
Antifriction rolling contact (Ball & Roller) Online greasing facility for all frames |
FEATURES | VALUES/ STANDARDS |
---|---|
Ambient Temperature | -10 to +50°C |
Altitude | Not exceeding 1000 m above mean sea level |
Atmosphere | Non corrosive & non hazardous |
Relative Humidity | Up to 100% |
Voltage | 6.6kV, 3.3kV, 11kV +/- 10% |
Frequency | 50Hz +/- 5% |
Combined Variation | +/-10% |
Duty | S1 (continuous) |
Service factor | 1.0 |
Construction Features
FEATURES | VALUES/ STANDARDS |
---|---|
Protection | IP 55 |
Type of cooling | IC 411 / |
Class of Insulation | F |
Temperature Rise | Class B for stator, Class F for rotor |
Terminal Box position | LHS from NDE |
Bearing | Roller Bearings at NDE, Ball bearings at DE |
Lubrication | Grease |
Mounting | IM 1001, IM 3011, IM 2001, IM 3001 |
Accessories | ACH, 6*simplex RTD, 2* Duplex RTD type BTD |
Frame sizes | 355 frame to 710 frame |
Shaft Extension | Single cylindrical extension as per IS:1231 |
Connection | Star |
Performance Features
FEATURES | VALUES/ STANDARDS |
---|---|
Method of starting | LRS/ STATOR-ROTOR |
Vibration | As per IS: 12075 |
Noise | As per IS: 12065 |
Fault withstand level of Terminal Box | 43.7kA for 0.25sec, 39.4kA for 0.25 sec(in case of 11kV supply voltage) |
Bearing Life | 40,000 working hours in case of direct drive. 20,000 working hours in case of belt drive. |
FEATURES | VALUES/ STANDARDS |
---|---|
Ambient Temperature | -10 to +50°C |
Altitude | Not exceeding 1000 m above mean sea level |
Atmosphere | Non corrosive & non hazardous |
Relative Humidity | Up to 100% |
Voltage | 6.6kV, 3.3kV, 11kV +/- 10% |
Frequency | 50Hz +/- 5% |
Combined Variation | +/-10% |
Duty | S1 (continuous) |
Service factor | 1.0 |
Construction Features
FEATURES | VALUES/ STANDARDS |
---|---|
Protection | IP 55 |
Type of cooling | IC 411 / |
Class of Insulation | F |
Temperature Rise | Class B for stator, Class F for rotor |
Terminal Box position | LHS from NDE |
Bearing | Roller Bearings at NDE, Ball bearings at DE |
Lubrication | Grease |
Mounting | IM 1001, IM 3011, IM 2001, IM 3001 |
Accessories | ACH, 6*simplex RTD, 2* Duplex RTD type BTD |
Frame sizes | 355 frame to 710 frame |
Shaft Extension | Single cylindrical extension as per IS:1231 |
Connection | Star |
Performance Features
FEATURES | VALUES/ STANDARDS |
---|---|
Method of starting | LRS/ STATOR-ROTOR/GRR |
Vibration | As per IS: 12075 |
Noise | As per IS: 12065 |
Fault withstand level of Terminal Box | 43.7kA for 0.25sec, 39.4kA for 0.25 sec(in case of 11kV supply voltage) |
Bearing Life | 40,000 working hours in case of direct drive. 20,000 working hours in case of belt drive. |
FEATURES | VALUES/ STANDARDS |
---|---|
Ambient Temperature | -10 to +50°C |
Altitude | Not exceeding 1000 m above mean sea level |
Atmosphere | Non corrosive & non hazardous |
Relative Humidity | Up to 100% |
Voltage | 415V, 690V, 6.6kV, 3.3kV, 11kV +/- 10% |
Frequency | 50Hz +/- 5% |
Combined Variation | +/-10% |
Duty | S1 (continuous) |
Service factor | 1.0 |
Construction Features
FEATURES | VALUES/ STANDARDS |
---|---|
Protection | IP 55 |
Type of cooling | IC 611/ 81W |
Class of Insulation | F / H |
Terminal Box position | LHS from NDE |
Bearing | Roller Bearings at NDE, Ball bearings at DE |
Lubrication | Grease |
Mounting | IM 1001, IM 3011, IM 2001, IM 3001 |
Accessories | ACH, 6*simplex RTD, 2* Duplex RTD type BTD |
Frame sizes | 355 frame to 710 frame |
Shaft Extension | Single cylindrical extension as per IS:1231 |
Connection | Star |
Performance Features
FEATURES | VALUES/ STANDARDS |
---|---|
Method of starting | LRS/ STATOR-ROTOR/GRR |
Vibration | As per IS: 12075 |
Noise | As per IS: 12065 |
Fault withstand level of Terminal Box | 43.7kA for 0.25sec, 39.4kA for 0.25 sec (in case of 11kV supply voltage) |
Bearing Life | 40,000 working hours in case of direct drive. 20,000 working hours in case of belt drive. |
FEATURES | VALUES/ STANDARDS |
---|---|
Ambient Temperature | -10 to +50°C |
Altitude | Not exceeding 1000 m above mean sea level |
Atmosphere | Non corrosive & non hazardous |
Relative Humidity | Up to 100% |
Voltage | 415V, 690V, 6.6kV, 3.3kV, 11kV +/- 10% |
Frequency | 50Hz +/- 5% |
Combined Variation | +/-10% |
Duty | S1 (continuous) |
Service factor | 1.0 |
Construction Features
FEATURES | VALUES/ STANDARDS |
---|---|
Protection | IP 55 |
Type of cooling | IC 611 / 616 / 8A1W7 |
Class of Insulation | F / H |
Terminal Box position | LHS from NDE |
Bearing | Roller Bearings at NDE, Ball bearings at DE |
Lubrication | Grease |
Mounting | IM 1001, IM 3011, IM 2001, IM 3001 |
Accessories | ACH, 6*simplex RTD, 2* Duplex RTD type BTD |
Frame sizes | 355 frame to 710 frame |
Shaft Extension | Single cylindrical extension as per IS:1231 |
Connection | Star |
Performance Features
FEATURES | VALUES/ STANDARDS |
---|---|
Method of starting | DOL |
Vibration | As per IS: 12075 |
Noise | As per IS: 12065 |
Fault withstand level of Terminal Box | 43.7kA for 0.25sec, 39.4kA for 0.25 sec(in case of 11kV supply voltage) |
Bearing Life | 40,000 working hours in case of direct drive. 20,000 working hours in case of belt drive. |
Particulars | |
---|---|
kW Range | 1.5 to 600 kW |
Frame Size | 112 to 560 |
GENERAL SPECIFICATIONS | |
---|---|
Standards | BS 5000/IS 4722 |
Insulation | Class F/Class H |
Armature Voltage | 110 to 1000 Volts |
Field Voltage | 180 to 360 Volts |
Cooling | IC 01/06/0041/0666/W37A86/17/44 |
Protection | IP 23/44/54 |
Mounting | B3/B35/B5/V1/V5 |
Particulars | |
---|---|
kW Range | 1.5 to 970 kW |
Frame Size | 802 to 824 |
GENERAL SPECIFICATIONS | |
---|---|
Standards | BS 5000/IS 4722 |
Insulation | Class F/Class H |
Armature Voltage | 110 to 1000 Volts |
Field Voltage | 180 to 360 Volts |
Cooling | IC 01/06/0041/0666/W37A86/17/44 |
Protection | IP 23/44/54 |
Mounting | B3/B35/B5/V1/V5 |